Research on Gas Protection Misoperation Mechanism and Strategy in Switching Process of On-Load Tap Changer for Large Capacity Transformer
on-load tap changer,flow velocity,gas protection,misoperation,strategy
Draft Accepted
Jianan Si / Xi’an Jiaotong University
Zhiguo Hao / Xi’an Jiaotong University
Ya Zhang / Xi’an Jiaotong University
Shaoyong Yao / Xi’an Jiaotong University
Guocheng Ding / State Grid Anhui Electric Power Co., LTD.
Xingwang Wu / State Grid Anhui Electric Power Co., LTD.
The arc generated when the on-load tap-changer (OLTC) is switched can cause the insulating oil inside the oil tank to surge. With the increase of transformer capacity, the oil
surge is very severe due to the large arc current during the switching process, and the gas protection misoperation accident occurs frequently. This paper first analyzes the characteristics of the oil flow velocity in the connecting pipe of oil conservator when faults of different severity occur, and then compares it with the oil flow velocity characteristics in the case of normal switching of OLTC. Finally, according to the difference of flow characteristics in two cases, two strategies for dealing with gas protection misoperation are proposed. One is to reset the settings of the gas protection, and the other is the delay strategy.
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information