782 / 2019-04-28 21:47:56
Research on Characteristics of Pole-to-Pole Fault in DC/DC Transformer with Fault Blocking Capability
DC/DC transformer,fault characteristic,fault blocking,pole-to-pole fault
Draft Accepted
DC/DC transformer with fault blocking capability can isolate fault without DC circuit breaker, which is an important research and development direction of DC system. Studying its fault characteristics is of great significance to ensure the safe operation of the power system. The working principle of hybrid modular multilevel DC/DC transformer with fault current blocking capability is analyzed, and the equivalent circuit models of DC/DC transformer before and after its blocking operation are studied. When the system has pole-to-pole fault on one side of the DC/DC transformer, the transient characteristics of electric quantities on both ports of DC/DC transformer before and after its blocking operation are studied. The analytical expressions of transient voltage and short circuit current of the fault port are studied and compared with the fault characteristics without blocking operation. Finally, PSCAD/EMTDC is used to build the simulation model and verify the analysis results.
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information