Optimized Demagnetization Control Strategy of Double Feed Induction Generator in Fault Ride Through Period
DFIG,Demagnetization Control,FRT,Rotor Transient Current,Stator Transient Flux
Draft Accepted
Jianjian Xu / Shan Dong University
Lei Ding / Shan Dong University
Xuesong Gao / Shan Dong University
In fault ride through (FRT) period, the stator side of double feed induction generator (DFIG) will generate a transient flux, which may cause the rotor overcurrent and the DC bus over voltage. The demagnetization control is an effective method to accelerate the decay of stator transient flux. But the effect of traditional demagnetization control is not ideal. In this paper, the transient model of DFIG is derived first. Then, an optimized demagnetization control strategy is proposed, and the performance of the proposed strategy is analyzed. The simulation results of a 2 MW DFIG system in DIgSILENT/Power Factory software validate that
the optimized demagnetization control strategy can accelerate the decay of stator transient flux more effectively than the traditional demagnetization control strategy.