850 / 2019-04-29 23:32:44
Single Terminal Traveling Wave Method for Hybrid Line Ground Fault Location Based on EEMD and SDEO
Ground Fault location,Hybrid line,Modulus wave velocity,EEMD-SDEO,Traveling wave
Draft Accepted
Jiaxin DUAN / Xi’an University of Science and Technology
Aiming at the problem that the double terminal detection point clock is not synchronized for the double terminal traveling wave method commonly used in hybrid line fault location, this paper proposes a single terminal fault location method for hybrid lines. The section positioning threshold is calculated by inversely calculating the formula of the modulus wave velocity to determine the section where the fault is located, thereby realizing the single terminal method fault location of the hybrid line. EEMD can solve the modal aliasing problem of EMD to achieve adaptive decomposition of signals, but introduces noise interference. For this issue, this paper proposes SDEO to demodulate the EEMD-decomposed traveling wave signal. Noise interference can be avoided while preserving wave head information to achieve accurate extraction of the wave head. The simulation results show that the proposed method can effectively solve the problem of hybrid line ground fault location.
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information