An Identification Method for Sympathetic Inrush Based on Substation-Area Information
ID:247 View Protection:ATTENDEE Updated Time:2020-11-11 12:10:14 Hits:323 Poster Presentation

Start Time:Pending(12)

Duration:Pending

Session:No Session »

No files

Abstract
Sympathetic inrush is a phenomenon that occurs in an in-service transformer (IT) when a nearby transformer is energized. The phenomenon can cause transformer differential protection to maloperate. Identification methods for sympathetic inrush have been proposed to deal with the problem. However, these methods are based on local information from the IT, while sympathetic inrush involves two or more transformers. Therefore, an identification method is proposed based on substation-area information. A substation-area differential current is defined and its second harmonic component is utilized to identify the sympathetic inrush. Simulation results by PSCAD/EMTDC show the proposed method can distinguish sympathetic inrush from internal faults and energization inrush effectively.
Keywords
differential protection,magnetizing inrush,substation-area information,sympathetic inrush,transformer protection
Speaker
Fang Peng
University of Jinan

Submission Author
Fang Peng University of Jinan
Yiqing Liu University of Jinan
Xingong Cheng University of Jinan
Submit Comment
Verify Code Change Another
All Comments
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information