Purpose/Aim
Basin insulator is the weakest insulation link in GIS, and its insulation performance largely depends on whether there are defects on the surface and interior of the basin and the surface of metal electrode. During the production, test, installation and operation of basin insulator, it is very easy to introduce latent defects such as gas gap, surface bulge or depression, conductive particles and so on for various reasons. These defects will cause sudden changes in the electric field near it, resulting in GIS equipment failure and affecting the stable operation of power system. The aim of this paper is to present a comprehensive evaluation method for latent defects of basin insulator in GIS.
Experimental/Modeling methods
The latent defects of GIS are screened by partial discharge detection, and the size and location of defects are further determined by X-ray detection. Based on the influence of various latent defects on GIS insulation deterioration, a comprehensive evaluation function is constructed, the harm degree of various defects is quantified, and the comprehensive evaluation and early warning identification of GIS latent defects are realized.
Results/discussion
Using the comprehensive evaluation method proposed in this paper, taking a 252kV GIS bus support insulator as the object, combined with its X-ray detection results, the harm degree of its latent defects is evaluated, and it is suggested to arrange power outage maintenance as soon as possible. The withstand voltage test verifies the effectiveness of the evaluation results of the method proposed in this paper.
Conclusions
The comprehensive evaluation method proposed in this paper considers the influence law of insulation defects such as air gap and micro crack on its flashover characteristics, and can comprehensively evaluate the harm degree of latent defects of GIS insulation. It is verified by an example that it has good engineering application value.
Keywords
GIS basin insulator,Latent defects,Comprehensive evaluation method,Defects
Speaker
Xi Yang
Hefei University of Technology

Submission Author
Guobao Zhang State Grid AnHui Electric Power Research Institute
Hengyang Zhao State Grid Anhui Electric Power CO.,LTD.
Wei Yang State Grid AnHui Electric Power Research Institute
Zhengyang Wu State Grid AnHui Electric Power Research Institute
Weiping Guan State Grid AnHui Electric Power Research Institute
Xi Yang Hefei University of Technology
Lijuan Zhu Hefei University of Technology
Submit Comment
Verify Code Change Another
All Comments
Important Date
  • Conference Date

    Sep 25

    2022

    to

    Sep 29

    2022

  • Aug 15 2022

    Early Bird Registration

  • Sep 10 2022

    Contribution Submission Deadline

  • Nov 10 2022

    Registration deadline

  • Nov 30 2022

    Draft paper submission deadline

  • Nov 30 2022

    Final Paper Deadline

Sponsored By
IEEE DEIS
Organized By
Chongqing University
Contact Information