Purpose/Aim
The structure and operating conditions of VSC transformer are different from those of power transformer and converter transformer. Compute the grounding current of the core and clamp accurately is helpful to evaluate the operation status of transformer.
Experimental/Modeling methods
A method for computing the earthing current of a transformer is proposed. Firstly, a geometric model is established to characterize each metal structure in the transformer. Secondly, a finite element model of electrostatic field is established and the partial capacitance matrix is calculated. The circuit simulation model of the transformer can be obtained from the partial capacitance matrix, by which the grounding current can be computed.
Results/discussion
The VSC transformer core ground shield is grounded through the clamp, so the clamp grounding current is greater than the core. The computed grounding currents of the core and clamp are 18 and 274mA respectively, which are basically close to the measured results of 18 and 258mA.
Conclusions
The grounding current of transformer core and clamp is mainly capacitive current. With a larger size of core and higher the voltage of inner winding, grounding current is greater.
 
Keywords
transformer,Electric field,circuit
Speaker
kejie huang
Electric Power Research Institute; China southern power grid

Submission Author
kejie huang Electric Power Research Institute; China southern power grid
Jianwei Cheng Electric Power Research Institute; China Southern Power Grid
Shuaibing Wang Electric Power Research Institute; China southern power grid
Lianwei Bao Electric Power Research Institute, CSG
Yutong Zhang Xi’an Jiaotong University
Yuan La Ltd;China Southern Power Grid Co.
Submit Comment
Verify Code Change Another
All Comments
Important Date
  • Conference Date

    Sep 25

    2022

    to

    Sep 29

    2022

  • Aug 15 2022

    Early Bird Registration

  • Sep 10 2022

    Contribution Submission Deadline

  • Nov 10 2022

    Registration deadline

  • Nov 30 2022

    Draft paper submission deadline

  • Nov 30 2022

    Final Paper Deadline

Sponsored By
IEEE DEIS
Organized By
Chongqing University
Contact Information