Insulating Void Defect Analysis of Onsite 252kV GIS by Employing Partial Discharge UHF Diagnosis and Industry CT
partial discharge,UHF,insulating spacer,void defect,2921,industry CT,analysis method
Final Paper
Yifan He / Research Institute of State Grid Zhejiang Electric Power Company
Xianjun Shao / Research Institute of State Grid Zhejiang Electric Power Company
Shao'an Wang / Research Institute of State Grid Zhejiang Electric Power Company
Feiran Li / Research Institute of State Grid Zhejiang Electric Power Company
In this paper, the insulating void defect inside the insulating spacer of onsite 252kV GIS is analyzed by ultra-high frequency (UHF) partial discharge (PD) diagnosed method and industry CT apparatus. The defect position of onsite GIS is located by using the time difference of arrival (TDOA) method of UHF signal. The pulse current method and UHF method is combined together to investigate the variation of PD signal by using the experimental regression in GIS experimental platform. Industry CT apparatus is used in order to verify the detection accuracy of PD detection and location method. It is shown that, the PD level above 115kV applied voltage is about 200pC and -12dBm under pulse current method and UHF method, respectively. A void with 1.285cm length and 0.447cm width is investigated in interface between insulating material and metal insert in insulating spacer. The PD detection example proposed in this paper is helpful for the PD diagnosis and risk assessment in GIS insulation.
Important Date
  • Conference Date

    Oct 22

    2017

    to

    Oct 25

    2017

  • Jan 04 2017

    Abstract Notification of Acceptance

  • Mar 10 2017

    Draft Paper Acceptance Notification

  • Jun 30 2017

    Final Paper Deadline

  • Oct 25 2017

    Registration deadline

Contact Information
  • ice********
  • +86*********