Comparison of Mounted Angles Between A Pair of 2/3 Coil-type AMF Electrodes in a 126 kV Single-break Vacuum Interrupter
13422,13638,13637
Final Paper
Weigang Feng / Shaanxi Baoguang Vacuum Electric Device Co., Ltd.
Dongli Bi / Shaanxi Baoguang Vacuum Electric Device Co., Ltd.
Quan Wang / Shaanxi Baoguang Vacuum Electric Device Co., Ltd.
Xiaofei Yao / School of Electrical Engineering,Xi’an Jiaotong University
Xiaoshe Zhai / School of Electrical Engineering,Xi’an Jiaotong University
Zhiyuan liu / State Key Laboratory of Electric Power Equipment, Xi’an Jiaotong University
The objective of this paper is to compare mounted angles between a pair of 2/3 coil-type AMF electrodes in a 126 kV single-break vacuum interrupter. Three kinds of mounted angles are assigned, which include 0°, 30°, and 60° slot shift between a pair of contact plates. A comparison of the mounted angles is made from the point of view of the distribution of axial magnetic flux density, the AC and DC resistance, the anode discharge mode, as well as the contact erosion pattern. The axial magnetic flux density, both in the intermediate plane of the electrode gap and on the contact plate under each mounted angle case, is compared. The AC and DC resistance for each case are also analyzed. A high-speed Charge Coupled Device (CCD) camera is used to determine the arc discharge mode under different mounted angle cases. The contact erosion condition is compared between different mounted angle cases, with each case is subjected to 6 interruptions of 40 kA arcing current.
Important Date
  • Conference Date

    Oct 22

    2017

    to

    Oct 25

    2017

  • Jan 04 2017

    Abstract Notification of Acceptance

  • Mar 10 2017

    Draft Paper Acceptance Notification

  • Jun 30 2017

    Final Paper Deadline

  • Oct 25 2017

    Registration deadline

Contact Information
  • ice********
  • +86*********